Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) SERVICE CONDUCTORS DO NOT MEET CLEARANCE REQUIREMENTS ABOVE ROOF PER NEC 230.24 AND 230.26 APPROVED AS DIRECTED BY RAY MAJUTA |
|
| 05/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WHERE IS GROUNDED (NEUTRAL) CONDUCTOR FOR FEED TO SUB-PANEL. IDENTIFY GROUNDED CONDUCTOR PER NEC 200.6 2. NEED TO MEET CLEARANCE REQUIREMENTS ABOVE ROOFS (8FT) PER NEC 230.24 & 230.36 |