Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BE ADVISED, COT INSPECTORS ARE NO LONGER ACCEPTING NON LISTED RISER CONDUIT BRACES MADE FROM EMT. BRACES MUST BE A LISTED ASSEMBLY PER 110 NEC 2) VERIFY PERMIT FOR NEW AC UNIT OBTAINED BY OWNER OR A/C CONTRACTOR 3) A BOND BUSHING WILL BE REQUIRED AT 3/4" CONDUIT TERMINATION INTO PANEL WHEN USING REDUCING WASHERS PER 250 NEC |