Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING PER NEC 230.28 CANNOT USE SMASHED EMT 2. ALL OTHER PREVIOUS INSPECTION ITEMS CORRECTED |
|
| 05/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING PER NEC 230.28 CANNOT USE EMT & MINERALLAC STRAPS 2. NEED MIN 8' CLEARANCE ABOVE ROOF PER NEC 230.24 3. USE PROPER FITTING FOR CONNECTION OF 1/2" LB TO PANEL -- NEC 110.3 4. NEED PANEL DIRECTORY PER NEC 408.4 NEEDS TO BE LEGIBLE 5. CUT STRANDS ON GROUND WIRE TO AC UNIT 6. CANNOT SEE INTO METER SECTION. METER INSTALLED & SERVICE ENERGIZED PRIOR TO APPROVALS. 7. INSTALL 2 POLE BREAKER FOR POOL PUMP OR INSTALL APPROVED HANDLE TIE ON SINGLE POLE BKRS. NEC 240.20 |