Permit: T07EL00828

Parcel: 128020600


Addresses:

6242 E 15TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/22/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING PER NEC 230.28
CANNOT USE SMASHED EMT
2. ALL OTHER PREVIOUS INSPECTION ITEMS CORRECTED
05/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING PER NEC 230.28
CANNOT USE EMT & MINERALLAC STRAPS
2. NEED MIN 8' CLEARANCE ABOVE ROOF PER NEC 230.24
3. USE PROPER FITTING FOR CONNECTION OF 1/2" LB TO PANEL -- NEC 110.3
4. NEED PANEL DIRECTORY PER NEC 408.4
NEEDS TO BE LEGIBLE
5. CUT STRANDS ON GROUND WIRE TO AC UNIT
6. CANNOT SEE INTO METER SECTION. METER INSTALLED & SERVICE ENERGIZED PRIOR TO APPROVALS.
7. INSTALL 2 POLE BREAKER FOR POOL PUMP OR INSTALL APPROVED HANDLE TIE ON SINGLE POLE BKRS. NEC 240.20