Permit: T07EL00827

Parcel: 134182270


Addresses:

7442 E CALLE ARTURO

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/11/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING PER NEC 230.28
CANNOT USE EMT & MINERALLAC STRAP.
2. RECONNECT GROUNDS TO TELEPHONE & CABLE
3. CANNOT SEE IN UPPER METER SECTION
METER INSTALLED & SERVICE ENERGIZED PRIOR TO APPROVALS.