Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MUST USE A LISTED AND APPROVED GUY SUPPORT SYSTEM ON MAST. 2. MUST VERIFY WIRE USED IN RISER IS RATED SUNLIGHT RESISTANT 3. IF YOU USE METAL CONDUIT TO PROTECT GROUND TO RODS IF MUST HAVE GROUND BUSHING AT EACH END TO PREVENT CHOKE EFFECT. |