Permit: T07EL00825

Parcel: 116125260


Addresses:

1544 W ONTARIO ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
#1 NOT COMPLIED WITH
#2 IS OK
#3 IS THERE A JUNCTION BOX INSIDE WHERE NEW WIRING GOES TO
#4 OK
#5 OK
#6 STILL HAVE GE BREAKERS IN ITE PANEL
#7 STRAPS USED ON 3/4" CONDUIT SHOULD BE 3/4" NOT 1"
05/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RISER SUPPORTS OF UNLISTED TYPE, USE APPROVED FITTING WITH RIGID CONDUITS.
2. SERVICE REQUIRES A GAS BOND
3. ACCOUNT FOR NEW WIRING FROM SERVICE INTO HOUSE WAS IT INSPECTED PRIOR?
4. DRIVE GROUND RODS TO GRADE
5. USE CORRECT SCREWS ON PANEL COVER AND DEAD FRONT COVER.
6. ALL BREAKERS TO BE SIEMENS ITE