Permit: T07EL00816

Parcel: 113061870


Addresses:

3215 N JACKSON AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/01/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- #3 CLEARANCE TO SERVICE INSUFFICIENT
- 3' OUT IN FRONT OF AT A LEVEL GRADE LAST BLOCK
RUN IN WAY
- #5 SEE NEC
05/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CORRECTIONS NOT COMPLETED
05/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY
1. IDENTIFY NEUTRAL WHERE IT LEAVES WEATHERHEAD -
NEC 200
2. INSTALL MAST BRACE AT AN ANGLE THAT WILL BE EFFECTIVE, NOT OFF TO THE SIDE AND SECURE FEET INTO STRUCTURE NOT JUST ROOF SHEATING - - NEC 230
3. SERVICE TO HAVE PROPER FRONT ENTRY CLEARANCE
NEC 110
4. DRIVE GROUND RODS INTO EARTH, NOT RAISED PLANTER BED -- NEC 250
5. NEUTRALS #6 AND SMALLER TO BE WHITE ENTIRE LENGTH NEC 200
6. SELF TAP SCREWS NOT ALLOWED FOR GROUND CONNECTION -- NEC 250
7. REMOVE PAINT UNDER GROUND LUGS -- NEC 250
8. W.P ENCLOSURE TO HAVE SEALING TYPE LOCKNUT FOR SIDE ENTRY -- NEC 110, 314
9. 2 GANG W.P BOX IS OVERFILLED -- NEC 314
10. PROVIDE ACCESS TO WATER/GAS BOND

THIS SERVICE HAS BEEN ENERGIZED BEFORE APPROVAL.