Permit: T07EL00813

Parcel: 131081580


Addresses:

6072 E 27TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/29/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL GROUND CLAMPS ON GROUND RODS LISTED FOR USE ON GROUND RODS & LISTED FROM DIRECT BURY.
2. INSTALL 2 CLAMPS ON RISER USING 1/4" HARDWARE
3. CANNOT BURY SPLICES BEHIND SERVICE PANEL. NEED TO BE ACCESSIBLE. CANNOT RUN THHN AS OPEN CONDUCTORS
4. NEED TO BURY #4 BETWEEN GROUND RODS
5. INSTALL SEALING WASHER ON PENETRATION INTO PANEL ABOVE BUS BARS (3/4" EMT)
6. INSTALL WEATHERPROOF BOX AT JUNCTION POINT FOR 1/2" EMT & 3/4" EMT
7. GROUND WIRE TO BE CONNECTED TO METAL BOX
8. CANNOT SEE INTO METER SECTION. METER INSTALLED & SERVICE ENERGIZED PRIOR TO APPROVALS.
9. MAST LOOKS TO BE CROOKED AND NEEDS TO BE SUPPORTED WITH LISTED MAST BRACING.
10. INSTALL METAL ADDRESS LABEL