Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) AT INTERIOR J-BOX: MAX 15 AMP ON #12 COPPER CLAD 2) USE PROPER SIZE GROUND TO GROUND BOX #12 CU 3) MAKE SURE CKTS WITH SHARED NEUTRAL TERMINATE ON SEPERATE PHASES 4) MUD RING TO BE FLUSH TO SURFACE (NOT SET BACK) WASHER-GROUND BOX 5) DRYER-USE A DEEP BOX AND GROUND IT, MOUNT RECEPTACLE SECURELY |
|
| 05/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :$ HAVE ELECTRICIAN WITH LADDER ON SITE FOR INSPECTION SERVICE ENERGIZED BEFORE APPROVAL |
|
| 05/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE A LISTED GUY KIT OR STIFF ARMS FOR MAST BRACE 2. SEAL FLASHING 3. GROUND RODS TO BE MINIMUM 6' APART & DRIVEN FLUSH 4. PROVIDE ACCESS TO ATTIC J-BOX 5. HAVE TOP SECTION OF SERVICE OPEN -- I COULD NOT PULL METER. |