Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/07/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. 2ND GROUND ROD TO BE 6' MIN. DISTANCE APART - NOT 2 1/2" 2. TIGHTEN LOOSE FITTINGS & LOCK NUTS 3. PLEASE PROVIDE A LADDER TO INSPECT JUNCTION BOX FOR MAKE UP AND BONDING 4. TIGHTEN LOOSE CONDUCTOR TERMINATIONS 5. PLEASE VERIFY PERMIT FOR NEW WATER HEATER INSTALLATION. |
|
| 05/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GATE LOCKED AT SIDE NO ANSWER AT DOOR |