Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2007 | ELECTRIC - FINAL | Approved | ||
| 08/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE CONDUCTORS FROM METER BASE TO WEATHERHEAD ARE STILL UNDERSIZED 3/0 AL NOT RATED FOR 200 AMP SERVICE 2. STILL NEED TO PROPERLY DERATE BRANCH CKT'S IN RACEWAY FROM PANEL TO J-BOX. READ NEC 310.15 WILL NEED TO PAY REINSPECTION FEE |
|
| 05/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY 1. NEUTRAL #6 AND SMALLER TO BE WHITE ENTIRE LENGTH NEC 200.6 2. EQUIPMENT GROUND #6 OR SMALLER TO BE GREEN OR BARE ENTIRE LENGTH -- NEC 250.119 3. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED -- NEC 408.4 4. NEUTRAL & GROUND NOT ALLOWED UNDER SAME TERMINATION - NEC 408.41 5. CONDUCTORS, RACEWAYS ENTERING RAINTIGHT ENCLOSURES TO BE RAINTIGHT -- NEC 314.15 (PANEL & J-B0X) 6. BRANCH CKT CONDUCTORS IN EMT TO J-BOX TO BE PROPERLY DERATED -- NEC 310.15 B 2 A 7. COMMON NEUTRAL TO SUPPLY NOT MORE THAN 2 BRANCH CKT'S, BRANCH CKT'S WITH COMMON NEUTRAL MUST TERMINATE ON SEPARATE PHASES -- NEC 100, NEC 210 8. DRIVE GROUND RODS FLUSH TO GRADE - NEC 250.53 G 9. STRAP FLEX LEAVING PANEL -- NEC 356.30 10. MAX 15 AMP ON 14CU OR #12 CIAD CONDUCTORS NEC 310, 240.4D 11. SERVICE DROP TO HAVE PROPER CLEARANCE TO GRADE NEC 230.24 B 12. NEED MINIMUM 4/0 AL OR 2/0 COPPER FOR SERVICE CONDUCTORS NEC 310.15 B6 13. NEED PERMIT FOR NEW HVAC |