Permit: T07EL00791

Parcel: 112070820


Addresses:

2539 N TREAT AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/22/2007 ELECTRIC - FINAL Approved
08/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE CONDUCTORS FROM METER BASE TO WEATHERHEAD ARE STILL UNDERSIZED 3/0 AL NOT RATED
FOR 200 AMP SERVICE
2. STILL NEED TO PROPERLY DERATE BRANCH CKT'S IN RACEWAY FROM PANEL TO J-BOX. READ NEC 310.15

WILL NEED TO PAY REINSPECTION FEE
05/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY
1. NEUTRAL #6 AND SMALLER TO BE WHITE ENTIRE LENGTH
NEC 200.6
2. EQUIPMENT GROUND #6 OR SMALLER TO BE GREEN OR BARE ENTIRE LENGTH -- NEC 250.119
3. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED --
NEC 408.4
4. NEUTRAL & GROUND NOT ALLOWED UNDER SAME TERMINATION - NEC 408.41
5. CONDUCTORS, RACEWAYS ENTERING RAINTIGHT ENCLOSURES TO BE RAINTIGHT -- NEC 314.15 (PANEL & J-B0X)
6. BRANCH CKT CONDUCTORS IN EMT TO J-BOX TO BE PROPERLY DERATED -- NEC 310.15 B 2 A
7. COMMON NEUTRAL TO SUPPLY NOT MORE THAN 2 BRANCH CKT'S, BRANCH CKT'S WITH COMMON NEUTRAL MUST TERMINATE ON SEPARATE PHASES -- NEC 100, NEC 210
8. DRIVE GROUND RODS FLUSH TO GRADE - NEC 250.53 G
9. STRAP FLEX LEAVING PANEL -- NEC 356.30
10. MAX 15 AMP ON 14CU OR #12 CIAD CONDUCTORS
NEC 310, 240.4D
11. SERVICE DROP TO HAVE PROPER CLEARANCE TO GRADE
NEC 230.24 B
12. NEED MINIMUM 4/0 AL OR 2/0 COPPER FOR SERVICE CONDUCTORS NEC 310.15 B6
13. NEED PERMIT FOR NEW HVAC