Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) SERVICE CONDUCTORS DO NOT MEET CLEARANCE REQUIREMENTS ABOVE ROOF PER NEC 230.24 & 230.26 APPROVED AS DIRECTED BY R. MAJUTA |
|
| 05/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROTECT CABLES COMING INTO 12" X 12" JUNCTION BOX THROUGH 3/4" EMT PER NEC 300.15(C) 2. IDENTIFY NEUTRAL CLOSER TO WEATHERHEAD 3. NEED CLEARANCE ABOVE ROOF, MIN. 8', PER NEC 230.24 & 230.26 4. PANEL TO BE FIRMLY SECURED TO SURFACE PER NEC 110.13 5. GROUND RODS & WATER & GAS BONDING OK 6. SERVICE ENERGIZED PRIOR TO CLEARANCE 7. EXPLAIN DRYER ON 2 POLE 20 AMP CIRCUIT |