Inspection History: ELECTRIC - FINAL

Permit Number - T07EL00779

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/22/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) SERVICE CONDUCTORS DO NOT MEET CLEARANCE REQUIREMENTS ABOVE ROOF PER NEC 230.24 & 230.26 APPROVED AS DIRECTED BY R. MAJUTA
05/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROTECT CABLES COMING INTO 12" X 12" JUNCTION BOX THROUGH 3/4" EMT PER NEC 300.15(C)
2. IDENTIFY NEUTRAL CLOSER TO WEATHERHEAD
3. NEED CLEARANCE ABOVE ROOF, MIN. 8',
PER NEC 230.24 & 230.26
4. PANEL TO BE FIRMLY SECURED TO SURFACE PER NEC 110.13
5. GROUND RODS & WATER & GAS BONDING OK
6. SERVICE ENERGIZED PRIOR TO CLEARANCE
7. EXPLAIN DRYER ON 2 POLE 20 AMP CIRCUIT