Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ALL CONDUCTORS OF THE SAME CIRCUIT NEED TO BE CONTAINED IN SAME RACEWAY OR CABLE. CANNOT RUN NEUTRAL FOR SUB-PANEL AS OPEN CONDUCTOR. NEC 300.3 |
|
| 05/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE OLD SERVICE CORRECTLY 2. FEED TO SUB-PANEL NEEDS TO HAVE PROPER SIZE NEUTRAL AND NEEDS TO BE INSULATED CONDUCTOR AND IDENTIFIED PROPERLY. NEC 200. |