Permit: T07EL00763

Parcel: 120072980


Addresses:

325 W DISTRICT ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/22/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/21/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/25/2008 ELECTRIC - FINAL Denied 1. SERVICE TO HIGH 6'7" MAX. HEIGHT TO BREAKER
2. USE #4 COPPER MIN. FOR RISER CONDUCTORS
3. SEE NOTES PREVIOUS INSP.
08/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL GROUND RODS 2 @ 6' APART
BOND WATER & GAS PIPING
2. RISER CONDUCTORS MUST BE MIN. #4 CU FOR 100 AMP
3. BUSHING REQUIRED BEHIND SERVICE PANEL TO PROTECT WIRING FROM ABRASION
4. USE 1/4" BOLTS MIN. FOR RISER SUPPORT
5. OLD CABLE NEEDS TO BE PROTECTED
6. TO MANY SPLICES IN GROUND WIRE
SEE ART 230 & 250 NEC