Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/21/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/25/2008 | ELECTRIC - FINAL | Denied | 1. SERVICE TO HIGH 6'7" MAX. HEIGHT TO BREAKER 2. USE #4 COPPER MIN. FOR RISER CONDUCTORS 3. SEE NOTES PREVIOUS INSP. |
|
| 08/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL GROUND RODS 2 @ 6' APART BOND WATER & GAS PIPING 2. RISER CONDUCTORS MUST BE MIN. #4 CU FOR 100 AMP 3. BUSHING REQUIRED BEHIND SERVICE PANEL TO PROTECT WIRING FROM ABRASION 4. USE 1/4" BOLTS MIN. FOR RISER SUPPORT 5. OLD CABLE NEEDS TO BE PROTECTED 6. TO MANY SPLICES IN GROUND WIRE SEE ART 230 & 250 NEC |