Inspection History Details
Permit: T07EL00753
Inspection Status: Cancelled
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2008 | ELECTRIC - SERVICE UPGRADE | Cancelled | CANCELLED PER DON ON STURGEON ELECTRIC #631-6114 | |
| 02/20/2008 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 02/07/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* PARTIAL SERVICE - INSPECTION ONLY 1. SERVICE SECONDARY RACEWAYS COVERED WITHOUT INSPECTION 2. BONDING CONDUCTORS UNDER SIZED - NEC 250.102 3. IDENTIFY SERVICE DISCONNECT AS SUCH - NEC 230.72B 4. SERVICE DISCONNECT DOOR TO OPEN 90 DEG. MINIMUM NEC 110 5. PROVIDE ILLUMINATION @ SERVICE - NEC 110 6. FUSES TO BE CHANGED 7. PROVIDE NEW GROUNDING ELECTRODE SYSTEM AND PIPE BONDING FOR SERVICE 8. PROVIDE LOADS FOR EXISTING SERVICE & EQUIPMENT DANNY DOBBS @ 444-5938 |