Permit: T07EL00753


Addresses:

311 E CONGRESS ST


Inspection Status: Cancelled

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07EL00753

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Cancelled

Date Description Inspector Results Comments
02/20/2008 ELECTRIC - SERVICE UPGRADE Cancelled CANCELLED PER DON ON STURGEON ELECTRIC #631-6114
02/20/2008 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
02/07/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*
PARTIAL SERVICE - INSPECTION ONLY

1. SERVICE SECONDARY RACEWAYS COVERED WITHOUT INSPECTION
2. BONDING CONDUCTORS UNDER SIZED - NEC 250.102
3. IDENTIFY SERVICE DISCONNECT AS SUCH - NEC 230.72B
4. SERVICE DISCONNECT DOOR TO OPEN 90 DEG. MINIMUM
NEC 110
5. PROVIDE ILLUMINATION @ SERVICE - NEC 110
6. FUSES TO BE CHANGED
7. PROVIDE NEW GROUNDING ELECTRODE SYSTEM AND PIPE BONDING FOR SERVICE
8. PROVIDE LOADS FOR EXISTING SERVICE & EQUIPMENT

DANNY DOBBS @ 444-5938