Permit: T07EL00750

Parcel: 134113350


Addresses:

8334 E KENYON DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/02/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
04/27/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETELY DRIVE GROUND RODS NEC 250.53
2. NEED MIN. 18" CLEARANCE ON SERVICE DROP
CONDUCTORS ABOVE OVERHANGING SECTION OF ROOF PER NEC 230.24
3. CANNOT INSTALL BOTH #14 GROUND WIRES UNDER ONE LUG NEC 110.3
4. MORE THAN 12 CURRENT CARRYING CONDUCTOS IN 3/4" EMT NEED TO DERATE BY 50% -- NEC 310.15