Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/27/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETELY DRIVE GROUND RODS NEC 250.53 2. NEED MIN. 18" CLEARANCE ON SERVICE DROP CONDUCTORS ABOVE OVERHANGING SECTION OF ROOF PER NEC 230.24 3. CANNOT INSTALL BOTH #14 GROUND WIRES UNDER ONE LUG NEC 110.3 4. MORE THAN 12 CURRENT CARRYING CONDUCTOS IN 3/4" EMT NEED TO DERATE BY 50% -- NEC 310.15 |