Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00738
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONNECTICUT ELECTRIC BREAKER IS NOT LISTED TO BE USED IN A SIEMENS PANEL SEE CIRCLED LABEL ON INSIDE COVER CHANGE OUT AND USE SIEMENS TYPE. |
|
04/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GAS METAL LINE ALSO REQUIRED TO BE BONDED 2. 2ND ROD TO GO TO GRADE 3. SIEMENS PNL DOES NOT LIST GE BREAKER 4. USE APPROVED LIST BRACE KIT -- NO EMT 5. WHITE CONDUCTOR ON AC TO BE TAPED BLACK OR RED 6. AC PERMIT? 7. EMT CONDUIT BEFORE IT GOES THRU ROOF TO BE INSTALLED ON COUPLING CORRECTLY, TIGHTEN FITTINGS, SUPPORT 3/4" EMT |