Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CAN'T LOCATE GROUND RODS 2. CAN'T LOCATE WATER BOND 3. VERIFY PROPER OVERCURRENT PROTECTION FOR SUB-PANEL FEEDER 4. PROVIDE ROOF ACCESS 5. NEED MECHANICAL PERMIT 6. INSTALL PROPER SIZE FUSES AND SERVICE RECEPTACLE FOR NEW AC (GFI WITHIN 25') |