Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE THE PROPER SIZE PLASTIC BUSHING BEHIND SERVICE PANEL WHERE WIRING EXITS. 2. STRAP #4 BARE TO WALL 3. BOND BUSHING REQUIRED ONE RISER CONDUIT, PER 250 NEC - SERVICE REENERGIZED PRIOR TO C.O.T CLEARANCE. |