Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/09/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) INSTALL PROTECTIVE BUSHINGS OVER 3/4" AND 1" EMT WERE WIRES ENTER 2) FILL OPENING IN BACK OF PANEL WERE WIRES ENTER WITH NON-COMBUSTIBLE MATERIAL 3) NEED PANEL DIRECTORY 4) INSTALL FILLER PLATE ON DEAD FRONT 5) CANNOT USE SPLIT BOLT CONNECTOR FOR MORE THAN 2 WIRES 6) FILL OPENING OF 1" EMT 7) RECALL WHEN READY |