Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) GAS CLAMP OR INVERTED BACK SIDE-OK 2) DID REMOVE RUST 3) HAD SOME TAPE-SHERE EXPOSED PART 4) SAME AS #3 5) DONE BY ? 6) WAS EXISTING 7) APPEARED OK 8) EC CLAIMS CLEAR TYPE WAS ON 9) ALL CB'S IN PANEL WHERE SIEMAN 10) #10 WAS NOT PER EC EXISTING CONDITION |
|
| 04/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL PROPER SIZE CLAMP 1" FOR GAS PIPE BOND NEC 250.70 2. REMOVE RUST AT CLAMP CONNECTION ON GAS NEC 250.12 3. IDENTIFY GROUNDING CONDUCTOR TO AC UNIT PER NEC 250.119 4. IDENTIFY NEUTRALS PER NEC 200.6 5. CONNECT GROUND WIRE TO BELL BOX PER NEC 250.148 6. IDENTIFY GROUNDING CONDUCTOR TO POOL EQUIPMENT PER NEC 250.119 7. CUT STRANDS ON NEUTRAL TO SUB-PANEL 8. INSTALL PENETRATOR AT ALUMINUM CONNECTIONS 9. INSTALL BKRS LISTED FOR USE IN SIEMENS PANEL NEC 110.3 10. NEUTRAL & GROUNDS TO BE SEPARATE AT SUB-PANEL NEC 250 11. INSTALL GROUND BAR AT SUB-PANEL FOR CONNECTION OF GROUND WIRES NEC 408.20 |