Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2007 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 05/08/2007 | ELECTRIC - RECONNECT | Cancelled | CANCELLED PER OWNER RITA #889-2194 | |
| 05/08/2007 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 05/07/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES -- #3, #8 LAST INSP. |
|
| 05/01/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. INSTALL GFI RECEPTACLES OVER KITCHEN SINK AREA 2. 240 RANGE RECEPTACLE WIRING NOT INSTALLED PER CODE 3. RANGE HOOD NOT WIRED PER CODE 4. SMOKE DETECTOR TO LOW, SHOULD BE BETWEEN 6"-12" BELOW CEILING. 5. EXPOSED WIRING IN BATHROOM 6. COVER PLATES FOR SWITCHES AND RECEPTS MISSING THROUGHOUT HOUSE. 7. SMOKE DETECTOR IN BEDROOM TO LOW & TOO CLOSE TO COOLER VENT OTHER BEDROOM SMOKE DETECTOR TO LOW. 8. ROMEX FOR PORCH & CARPORT NOT TO CODE ALSO, FLUORESCENT LIGHT NOT CODE. 9. CIRCUIT BREAKERS IN SERVICE PANEL NEED TO BE SAME MANUF. (BRAND) AS PANEL. |