Permit: T07EL00708

Parcel: 12315101A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL00708

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK UNIT 126
OK RECN
07/14/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEED REVISED & APPROVED PLANS FOR ALL ITEMS INSTALLED FOR THIS PROJECT
05/21/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
UNIT #126 LOCKED. NO ACCESS.
05/16/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/12/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
09/18/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK FINALS UNITS #226 & #229
09/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK FINAL UNIT #228
09/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION #229, 228, 226 ONLY

UNITS TO BE OPEN FOR INSPECTION
1. UNIT #229 HAS IMPROPERLY SIZED CONDUCTORS TO HOT WATER HEATER
2. UNIT #228 NO A.C
3. UNIT #226 UNDERSIZED WATER HEATER CKT, BROKEN HANDLE ON SERVICE DISCONNECT, AC MISSING


WORK TO BE DONE BY QUALIFIED ELECTRICIAN TRY TO LOCATE PROPER SERVICE DISCONNECT COVERS
09/05/2007 ELECTRIC - FINAL Partial Approval
05/14/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FOLLOWING UNITS REQUIRE CIRCUIT BREAKER COVERS AT SERVICES #127, 126, 226, 229, 230
2. #126 - MISSING RESECURE RANGE OUTLET BOX, INSTALL COVER, INSTALL MISSING RECEPTACLE COVERS, MISSING AC UNIT
3. #127 -- MISSING RANGE OUTLET COVER
4. #226 - MISSING WATER HEATER NOT CONNECTED, MISSING LIGHT OVER KITCHEN; AC UNIT HAS NO COVER
5. #228 NO WATER HEATER; NO AC
6. #229 IMPROPER CONNECTION AT WATER HEATER, NO AC UNIT
7. #222 WATER HEATER MISSING, SMOKE DETECTOR MISSING, AC UNIT MISSING, REPAIR KIT EXHAUST, KEY DOES NOT OPEN
8. THE GROUNDING SYSTEM HAS BEEN CUT AND REMOVED AT NORTH SERVICE ALSO, AT SOUTH SERVICE.