Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00707
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND SYSTEM TO SERVICE HAS BEEN CUT & REMOVED 2. MAJORITY OK MAIN CIRCUIT BREAKER COVERS MISSING 3. #213 MISSING CIRCUIT BREAKER COVER, MISSING WATER HEATER BREAKER, MISSING WATER HEATER AND AC UNIT, MISSING SMOKE DETECTOR AND RECEPTACLE COVERS, MISSING KIT LIGHT. 4. #117 NO SMOKE DETECTOR, NO KIT LIGHT 5. #219 MISSING AC UNIT AND RECEPTACLE COVER 6. ALL SERVICES HAVE HAD THE GROUNDING SYSTEMS CUT AND REMOVED. |