Permit: T07EL00704

Parcel: 136345580


Addresses:

3610 S CHESIN DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/27/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ITEMS #3 & #4 FROM INSPECTION ON 5/2/07
2. NEED TO BOND EACH END OF 3/4" EMT TO GROUNDING ELECTRODE CONDUCTOR PER NEC 250.64
3. SEAL OPEN KNOCKOUT BOTTOM OF PANEL
4. INSTALL #10 GROUND WITH 30 AMP CIRCUIT TO POOL EQUIPMENT.
05/02/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) FINISH TYING OFF BRANCH CIRCUITS
2) SECURE #4 TO BLDG SURFACE AND BOND WATER PIPE
3) INSTALL PANEL DIRECTORY PER NEC 408.4
4) LABEL SERVICE DISCONNECT
5) RECALL WHEN ALL WORK COMPLETE