Permit: T07EL00700

Parcel: 122132360


Addresses:

4015 E LEE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/01/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE.
2. RISER HARDWARE TO BE 1/4" MINIMUM
3. USE A LISTED BRACE KIT
4. WHERE IS GAS BOND?
5. PLEASE VERIFY DERATING AS PER 310.15 & 310.16
6. LABEL BREAKERS AS PER 408.4 -- ABBREVIATIONS NOT ALLOWED.
7. PLEASE PROVIDE ACCESS TO INSPECT WORK AT ROOF

NOTE: 100 AMP SERVICE IS BACK FED WITH A 12-2 CORD