Permit: T07EL00694

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T07EL00694

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
06/08/2007 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
06/07/2007 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
05/02/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OUTSIDE LIGHTING CONDUIT EAST, COME OFF BLD
2. ALL UNITS - REPLACE BATTERIES ON SMOKE DETECTORS
3. KITCHEN COUNTER AREAS - RECEPTACLES TO BE GFI PROTECTED.
4. BATHROOM RECEPTACLES TO BE GFI PROTECTED
5. REMARK CLEARLY PANEL SCHEDULES
6. WIRING IN PANEL 110 WIRING FOR AC UNIT HAS INSULATION BURNT OFF -- APPEARS TO HAVE HAD A HEATING PROBLEM PANEL - COLLECTION OF DUST & DIRT ON TERMINATIONS AND BUSS PARTS -- MOST PNLS HAVE NEVER BEEN CLEANED, NEED TO HAVE PANELS CLEANED AND TERMINALS RETIGHTENED CHECK ALL BREAKERS OFF & ON
7. OUTSIDE FIXTURES BROKEN ONES TO BE REPLACED
8. CHECK EXHAUST FANS ABOVE STOVES SOME DO NOT APPEAR READY FOR POWER -- TOO OLD
9. SOME UNIT FIXTURES ARE MISSING
10. SOME UNITS HAVE IMPROPERLY INSTALLED LIGHTING (111)
11. POOL OVERHEAD SERVICE CONDUCTORS IN HAZARDOUS SITUATION
12. CANNOT REVIEW POOL PANEL DUE TO OBSTRUCTION
13. OPEN PANEL AT METER LOCATION INSIDE
14. OUTSIDE METERS & CIRCUIT BREAKERS TO BE UNIT MARKED PERMANENTLY
15. NEED TO HAVE ELECTRICIAN REVIEW - REPAIR AND MAKE UNITS READY FOR OCCUPANCY
16. SOME AC SWITCHES & CONDUITS ON ROOF NEED RESUPPORTING

OVERALL OK