Permit: T07EL00685

Parcel: 117070860


Addresses:

534 S HERBERT AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL00685

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) ADDITIONAL PERMIT OBTAINED FOR ALL TRADES FOR THIS ADDRESS #T07CM02768
05/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEW WIRING IN BUILDING
2. IMPROPER GROUNDING AT SERVICE
3. SERVICE IS ON A HOUSE IT DOES NOT FEED, AND IS AN INDIVIDUAL ALL IN ONE.
4. REQUESTED AN ELECTRICAL CONTRACTOR TO CORRECT ITEMS -- LAST INSPECTION
04/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE REQUIRES ITS OWN NEW GROUNDING SYSTEM & GAS AND WATER
2. ADDRESS SERVICE
3. TOO MANY CURRENT CARRYING CONDUCTORS IN CONDUIT, SEE DERATING FACTORS IN 2002 NEC 310.15
4. CIRCUITS NOT SPLICED IN J-BOX
5. LB'S NEED COVERS
6. CONDUIT TO J-BOX TO BE SECURED
7. SECURE J-BOX PROPERLY
8. LABEL CIRCUITS
9. NO 15A CIRCUITS IN PANEL?
10. #10' WIRES IN J-BOX NO 30A CB'S IN PANEL
11. WHAT IS A 50A CB IN PNL FOR?
12. OBTAIN A LICENSED ELECTRICAL CONTRACTOR TO DO WORK AS PER REGISTRAR REQUIREMENTS
13. NEED TO SEE INSIDE SPLICING