Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00685
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) ADDITIONAL PERMIT OBTAINED FOR ALL TRADES FOR THIS ADDRESS #T07CM02768 |
|
05/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEW WIRING IN BUILDING 2. IMPROPER GROUNDING AT SERVICE 3. SERVICE IS ON A HOUSE IT DOES NOT FEED, AND IS AN INDIVIDUAL ALL IN ONE. 4. REQUESTED AN ELECTRICAL CONTRACTOR TO CORRECT ITEMS -- LAST INSPECTION |
|
04/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE REQUIRES ITS OWN NEW GROUNDING SYSTEM & GAS AND WATER 2. ADDRESS SERVICE 3. TOO MANY CURRENT CARRYING CONDUCTORS IN CONDUIT, SEE DERATING FACTORS IN 2002 NEC 310.15 4. CIRCUITS NOT SPLICED IN J-BOX 5. LB'S NEED COVERS 6. CONDUIT TO J-BOX TO BE SECURED 7. SECURE J-BOX PROPERLY 8. LABEL CIRCUITS 9. NO 15A CIRCUITS IN PANEL? 10. #10' WIRES IN J-BOX NO 30A CB'S IN PANEL 11. WHAT IS A 50A CB IN PNL FOR? 12. OBTAIN A LICENSED ELECTRICAL CONTRACTOR TO DO WORK AS PER REGISTRAR REQUIREMENTS 13. NEED TO SEE INSIDE SPLICING |