Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/08/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED MORE DETAILED PANEL DIRECTORY - NEC 408.4 2. PROTECT WIRE IN 1/2" EMT FROM ABRASION PER NEC 300.15 & 312.5 AND SEAL OPEN PIPE 3. INSTALL 2 GROUND RODS PER SECTION 3 OF NEC 250 4. INSTALL BREAKERS LISTED FOR USE IN PANEL - NEC 110.3 5. SERVICE ENERGIZED PRIOR TO APPROVAL 6. WHERE IS NEUTRAL CONDUCTOR FOR DRYER CIRCUIT? 7. INSTALL SEALING WASHERS ON CONDUIT ENTRANCES ABOVE ENERGIZED BUS SECTIONS. |