Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/12/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/08/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED MORE DETAILED PANEL DIRECTORY - NEC 408.4
2. PROTECT WIRE IN 1/2" EMT FROM ABRASION PER
NEC 300.15 & 312.5 AND SEAL OPEN PIPE
3. INSTALL 2 GROUND RODS PER SECTION 3 OF NEC 250
4. INSTALL BREAKERS LISTED FOR USE IN PANEL - NEC 110.3
5. SERVICE ENERGIZED PRIOR TO APPROVAL
6. WHERE IS NEUTRAL CONDUCTOR FOR DRYER CIRCUIT?
7. INSTALL SEALING WASHERS ON CONDUIT ENTRANCES ABOVE ENERGIZED BUS SECTIONS.