Permit: T07EL00667

Parcel: 133251470


Addresses:

8526 E HAWTHORNE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/08/2010 ELECTRIC - FINAL Approved
12/07/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WATER BOND TO BE TO INTERIOR SIDE OF PIPING ALSO GAS BOND.
2. PLEASE VERIFY 2ND GROUND ROD
3. SECURE GROUNDING ELECTRODE CONDUCTOR AND BONDING CONDUCTOR TO STRUCTURE
4. RISER HARDWARE TO BE 1/4" MINIMUM
5. A PERMANENT METAL ADDRESS LABEL IS NEEDED
6. IDENTIFY GROUNDED CONDUCTOR
7. SEPARATE GROUNDING EQUIPMENT CONDUCTORS AND INSTALL PER MANUFACTURES INSTRUCTIONS.
8. AN ANTI-OXIDE COMPOUND IS NEEDED FOR ALL ALUMINUM CONDUCTORS.
9. SEAL ENTRANCES WITH AN APPROVED DEVICE ABOVE CURRENT CARRING PARTS.
10. TIGHTEN LOOSE FITTINGS
11. LABEL BREAKERS
12. RECEPTACLE COVER TO BE WEATHERPROOF PER 406.8
13. INSTALL ALL STRAND OF CONDUCTOR UNDER TERMINALS
14. PLEASE VERIFY PERMITS FOR NEW WIRING AND CANS TO INTERIOR.
15. THIS IS AN UNOCCUPIED HOME PLEASE VERIFY QUALIFIED ELECTRICAL CONTRACTOR.