Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2010 | ELECTRIC - FINAL | Approved | ||
| 12/07/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WATER BOND TO BE TO INTERIOR SIDE OF PIPING ALSO GAS BOND. 2. PLEASE VERIFY 2ND GROUND ROD 3. SECURE GROUNDING ELECTRODE CONDUCTOR AND BONDING CONDUCTOR TO STRUCTURE 4. RISER HARDWARE TO BE 1/4" MINIMUM 5. A PERMANENT METAL ADDRESS LABEL IS NEEDED 6. IDENTIFY GROUNDED CONDUCTOR 7. SEPARATE GROUNDING EQUIPMENT CONDUCTORS AND INSTALL PER MANUFACTURES INSTRUCTIONS. 8. AN ANTI-OXIDE COMPOUND IS NEEDED FOR ALL ALUMINUM CONDUCTORS. 9. SEAL ENTRANCES WITH AN APPROVED DEVICE ABOVE CURRENT CARRING PARTS. 10. TIGHTEN LOOSE FITTINGS 11. LABEL BREAKERS 12. RECEPTACLE COVER TO BE WEATHERPROOF PER 406.8 13. INSTALL ALL STRAND OF CONDUCTOR UNDER TERMINALS 14. PLEASE VERIFY PERMITS FOR NEW WIRING AND CANS TO INTERIOR. 15. THIS IS AN UNOCCUPIED HOME PLEASE VERIFY QUALIFIED ELECTRICAL CONTRACTOR. |