Permit: T07EL00665

Parcel: 13621111A


Addresses:

7450 E BROOKS DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT SEE BONDING OF SERVICE RISER. METER INSTALLED AND SERVICE ENERGIZED.
2. BONDING JUMPER TO CLOSE NIPPLE NOT SIZED PROPERLY PER NEC 250.102
3. NEED TO BOND WATER PIPE. CANNOT TELL WHAT
EXISTING #4 GOES TO
4. LABEL PANEL DIRECTORY PER NEC 408.4
5. MARK SERVICE DISCONNECT PER NEC 230.70

TO AVOID REFEE HAVE ALL ITEMS COMPLETE
FOR NEXT INSPECTION.
04/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LABEL CIRCUITS PER NEC 408.4
2. INSTALL MAIN BONDING JUMPER PER NEC 250.28
3. BOND CLOSE NIPPLE PER NEC 250.92
4. BOND SERVICE RISER PER NEC 250.92
5. INSTALL GROUNDING ELECTRODE SYSTEM PER NEC 250.50, 250.52, 250.53, 250.54, 250.56, 250.62, 250.64, 250.66
6. BOND GAS & WATER PIPING PER NEC 250.104
7. MARK SERVICE DISCONNECT PER NEC 230.70