Permit: T07EL00624

Parcel: 134111040

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/01/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) COMPLETE ITEM #5 FROM INSPECTION OF 4/11/07
04/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND RODS TO BE MIN. 6' APART -- NEC 250.53
2. INSTALL PIPE GROUND CLAMPS ON PIPES NOT FITTINGS
AND INSTALL ON CLEAR SURFACE PER NEC 250.12
3. NEUTRAL CONDUCTOR #6 & SMALLER TO BE MARKED CONTINUOUSLY PER NEC 200.6
4. PROTECT CABLES IN 1" EMT PER NEC 300.15 & 312.5
5. INSTALL BREAKERS LISTED FOR USE IN PANEL. SEE PANEL DOOR.