Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) COMPLETE ITEM #5 FROM INSPECTION OF 4/11/07 |
|
| 04/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RODS TO BE MIN. 6' APART -- NEC 250.53 2. INSTALL PIPE GROUND CLAMPS ON PIPES NOT FITTINGS AND INSTALL ON CLEAR SURFACE PER NEC 250.12 3. NEUTRAL CONDUCTOR #6 & SMALLER TO BE MARKED CONTINUOUSLY PER NEC 200.6 4. PROTECT CABLES IN 1" EMT PER NEC 300.15 & 312.5 5. INSTALL BREAKERS LISTED FOR USE IN PANEL. SEE PANEL DOOR. |