Permit: T07EL00620

Parcel: 134082470


Addresses:

708 S CAMINO SECO

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/13/2007 ELECTRIC - FINAL Approved OWNER TO DRIVE GROUND RODS TO GRADE
OK TO CLEAR WILL NOTIFY TEP
04/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED MIN. 8' CLEARANCE ABOVE ROOF PER NEC 230.24
2. GROUND RODS TO BE MIN. 6' APART PER
NEC 250.56 & 250.53
3. GROUND RODS TO BE COMPLETELY DRIVEN PER NEC 250.53
4. PLEASE VERIFY GAS & WATER BOND
5. INSTALL BREAKERS LISTED TO BE USED IN PANEL
SEE PANEL DOOR
6. LABEL CIRCUITS PER NEC 408.4
7. SERVICE ENERGIZED PRIOR TO CLEARANCE