Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2007 | ELECTRIC - FINAL | Approved | OWNER TO DRIVE GROUND RODS TO GRADE OK TO CLEAR WILL NOTIFY TEP |
|
| 04/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED MIN. 8' CLEARANCE ABOVE ROOF PER NEC 230.24 2. GROUND RODS TO BE MIN. 6' APART PER NEC 250.56 & 250.53 3. GROUND RODS TO BE COMPLETELY DRIVEN PER NEC 250.53 4. PLEASE VERIFY GAS & WATER BOND 5. INSTALL BREAKERS LISTED TO BE USED IN PANEL SEE PANEL DOOR 6. LABEL CIRCUITS PER NEC 408.4 7. SERVICE ENERGIZED PRIOR TO CLEARANCE |