Permit: T07EL00618

Parcel: 111051310

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/24/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/14/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WHEN UPGRADING SUB-PANEL
NOT ALLOWED IN CLOSET
2. WE HAVE MULTIPLE TERMINATIONS UNDER LUG
3. CORRECTLY PROPORTION LOADS TO PHASE
4. SPLICES TO BE ACCESSIBLE -- NOT BEHIND SUB-PANEL
5. LABEL CIRCUIT BREAKERS
6. TIGHTEN LOOSE FITTINGS
05/02/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ADDRESS STILL DOES NOT MATCH PERMIT
2. UNIT TO BE OPEN FOR INSPECTION
3. DO NOT CALL BEFORE ALL CORRECTIONS HAVE BEEN COMPLETED OR A FEE WILL BE CHARGED

PERMIT, SERVICE, STRUCTURE TO ALL HAVE SAME ADDRESS!
04/25/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL CORRECT ADDRESS ON PERMIT & SERVICE & BUILDING
2. MIN. SIZE GROUND 30 AMP CKT #10 CU
3. #6 & SMALLER NEUTRAL TO BE WHITE ENTIRE LENGTH
4. BOND WATER & GAS PIPES TO SERVICE
5. NEED CONNECTOR FOR CABLE ENTERING 2 GANG W.P BOX
6. MAX. 15 AMP BREAKER #12 COPPER CIAD CONDUCTOR
7. HAVE 3-WIRE RECEP'S ON 2 WIRE CKT'S
8. NEED SMOKE DETECTORS IN BEDROOMS & HALL
9. PERMITS FOR WORK?
10. GFI PROTECTION WHERE REQUIRED.