Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/14/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WHEN UPGRADING SUB-PANEL NOT ALLOWED IN CLOSET 2. WE HAVE MULTIPLE TERMINATIONS UNDER LUG 3. CORRECTLY PROPORTION LOADS TO PHASE 4. SPLICES TO BE ACCESSIBLE -- NOT BEHIND SUB-PANEL 5. LABEL CIRCUIT BREAKERS 6. TIGHTEN LOOSE FITTINGS |
|
| 05/02/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ADDRESS STILL DOES NOT MATCH PERMIT 2. UNIT TO BE OPEN FOR INSPECTION 3. DO NOT CALL BEFORE ALL CORRECTIONS HAVE BEEN COMPLETED OR A FEE WILL BE CHARGED PERMIT, SERVICE, STRUCTURE TO ALL HAVE SAME ADDRESS! |
|
| 04/25/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL CORRECT ADDRESS ON PERMIT & SERVICE & BUILDING 2. MIN. SIZE GROUND 30 AMP CKT #10 CU 3. #6 & SMALLER NEUTRAL TO BE WHITE ENTIRE LENGTH 4. BOND WATER & GAS PIPES TO SERVICE 5. NEED CONNECTOR FOR CABLE ENTERING 2 GANG W.P BOX 6. MAX. 15 AMP BREAKER #12 COPPER CIAD CONDUCTOR 7. HAVE 3-WIRE RECEP'S ON 2 WIRE CKT'S 8. NEED SMOKE DETECTORS IN BEDROOMS & HALL 9. PERMITS FOR WORK? 10. GFI PROTECTION WHERE REQUIRED. |