Permit: T07EL00615

Parcel: 122080690


Addresses:

2230 N SYCAMORE BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CANNOT ENTER THROUGH METER SECTION PER MANUFACTURES LISTING.
2. CANNOT USE NEUTRAL FOR BONDING. THIS IS AN UNINSULATED NEUTRAL ON AN UNGROUNDED SYSTEM.
3. RISER HARDWARE TO BE 1/4" MINIMUM
4. USE A LISTED BRACE KIT
5. TIGHTEN LOOSE FITTINGS
6. PROPERLY SUPPORT PVC CONDUIT
7. LABEL BREAKERS AS PER 408.4 -- NO ABBREVIATIONS