Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CANNOT ENTER THROUGH METER SECTION PER MANUFACTURES LISTING. 2. CANNOT USE NEUTRAL FOR BONDING. THIS IS AN UNINSULATED NEUTRAL ON AN UNGROUNDED SYSTEM. 3. RISER HARDWARE TO BE 1/4" MINIMUM 4. USE A LISTED BRACE KIT 5. TIGHTEN LOOSE FITTINGS 6. PROPERLY SUPPORT PVC CONDUIT 7. LABEL BREAKERS AS PER 408.4 -- NO ABBREVIATIONS |