Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/13/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SIZE BONDING JUMPER ON SUPPLY SOUTH SIDE OF SERVICE DISCONNECT PER NEC 250.102(C) BONDING JUMPER TO BE #4 OK TO CLEAR INCR RESIDENTIAL 2. SERVICE CONDUCTORS ABOVE ROOF NEED TO MEET CLEARANCE PER NEC 230.24 |
|
| 04/10/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |