Permit: T07EL00611

Parcel: 128051600


Addresses:

5602 E 20TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SIZE BONDING JUMPER ON SUPPLY SOUTH SIDE OF SERVICE DISCONNECT PER NEC 250.102(C)
BONDING JUMPER TO BE #4

OK TO CLEAR INCR RESIDENTIAL

2. SERVICE CONDUCTORS ABOVE ROOF NEED TO MEET CLEARANCE PER NEC 230.24
04/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*