Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* NO ACCESS TO BACKYARD. GATES LOCKED. RANG DOORBELL. NO ANSWER. |
|
| 04/24/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. USE AN APPROVED FITTING WITH LB - CHASE NIPPLE NOT APPROVED. 2. USE A SEALING DEVICE FOR ENTRANCES ABOVE CURRENT CARRING PARTS 3. PLEASE LEAVE PREVIOUS WRITE UPS ON SITE |
|
| 04/23/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CANNOT ENTER THRU TOP OF PANEL 2) BOND AROUND GAS UNION 3) LABEL BREAKERS 4) USE TERMINAL ENDS WITH STRANDED CONDUCTORS 5) IDENTIFY NEUTRAL IN JUNCTION BOX |