Permit: T07EL00604

Parcel: 113031940


Addresses:

926 E WEYMOUTH ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/01/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CALL WHEN CHANGE OVER COMPLETE
04/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GUY TO BE USED AS LISTED (NEC 110.3 B) DO NOT USE CONNECTORS. BRACES TO BE THREADED INTO FEET.
2. DRIVE GROUND RODS SO THEY ARE FLUSH WITH THE GRADE AROUND THEM -- NOT STICKING UP.

THERE WILL BE A FEE IF NOT CORRECT NEXT INSPECTION.
04/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. SEAL FLASHING
2. USE A LISTED GUY KIT OR STIFF ARMS FOR MAST BRACE AND SECURE INTO TRUSSES -- EMT NOT ALLOWED.
3. DRIVE GROUND RODS FLUSH AND SECURE TO STRUCTURE OR BURY GROUNDING ELECTRODE CONDUCTOR.
4. NEED MECHANICAL PERMIT