Permit: T07EL00596

Parcel: 113112260


Addresses:

1718 E LINDEN ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL00596

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/29/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CORRECTIONS NOT COMPLETED
ALSO, STILL NEED PERMIT AND INSPECTION FOR NEW INTERIOR WIRING.

DO NOT CALL BEFORE THESE THINGS ARE COMPLETED OR A FEE WILL BE CHARGED.
05/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CIRCUITS WITH SHARED NEUTRAL TO TERMINATE ON DIFFERENT PHASES TO PREVENT OVERHEATING OF NEUTRAL
2. SECURE BACK SIDE OF MAST BRACE INTO STRUCTURE (TRUSS) NOT JUST ROOF SHEETING.
3. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED
4. NEED SEALING TYPE LOCKNUT FOR RACEWAY IN SIDE OF PANEL
5. BOND GAS PIPE
6. ADD NEW INTERIOR WIRING TO PERMIT FOR INSPECTION.