Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CORRECTIONS NOT COMPLETED ALSO, STILL NEED PERMIT AND INSPECTION FOR NEW INTERIOR WIRING. DO NOT CALL BEFORE THESE THINGS ARE COMPLETED OR A FEE WILL BE CHARGED. |
|
| 05/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CIRCUITS WITH SHARED NEUTRAL TO TERMINATE ON DIFFERENT PHASES TO PREVENT OVERHEATING OF NEUTRAL 2. SECURE BACK SIDE OF MAST BRACE INTO STRUCTURE (TRUSS) NOT JUST ROOF SHEETING. 3. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED 4. NEED SEALING TYPE LOCKNUT FOR RACEWAY IN SIDE OF PANEL 5. BOND GAS PIPE 6. ADD NEW INTERIOR WIRING TO PERMIT FOR INSPECTION. |