Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/09/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BURRY GROUNDING ELECTRODE CONDUCTOR NEC 250.64 2) SECURE WATER AND GAS BOND TO BLDG NEC 250.64 3) CANNOT USE SHEET METAL SCREW FOR CONNECTION FO GROUND TO 6" X 6" JUNCTION BOX NEC 250.8 4) REMOVE PAINT AT GROUND CONNECTION IN 6" X 6" JUNCTION BOX NEC 250.12 5) CLEAN SWITCHES AT GROUND CONNECTION WIRES AND GAS NEC 250.12 6) INSTALL PROTECTION ON EMT WERE 10/3 ROMEX ENTERS PER NEC 300.15 7) USE LISTED CONDUIT CONNECTION AT ENTRANCE TO PANEL. CANNOT USE CHASE NIPPLE 1" EMT 8) KINK IN 1" EMT AT 90 DEGREE ELBOW NEC 358.24 |