Permit: T07EL00594

Parcel: 131042930


Addresses:

4726 E 26TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/12/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
04/09/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BURRY GROUNDING ELECTRODE CONDUCTOR NEC 250.64
2) SECURE WATER AND GAS BOND TO BLDG NEC 250.64
3) CANNOT USE SHEET METAL SCREW FOR CONNECTION FO GROUND TO 6" X 6" JUNCTION BOX NEC 250.8
4) REMOVE PAINT AT GROUND CONNECTION IN 6" X 6" JUNCTION BOX NEC 250.12
5) CLEAN SWITCHES AT GROUND CONNECTION WIRES AND GAS NEC 250.12
6) INSTALL PROTECTION ON EMT WERE 10/3 ROMEX ENTERS PER NEC 300.15
7) USE LISTED CONDUIT CONNECTION AT ENTRANCE TO PANEL. CANNOT USE CHASE NIPPLE 1" EMT
8) KINK IN 1" EMT AT 90 DEGREE ELBOW NEC 358.24