Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEE NOTES #1 & 2 LAST INSP. CONVERTOR DAMAGED 2. INSTALL BUSHING AT END OF 3/4" SLEEVE TO PROTECT ROMEX FROM ABRASION 3. RECEPTS IN GARAGE TO BE GFI PROTECTED 4. CODE REQUIRES 6" OF CONDUCTOR LENGTH AT DEVICE BOXES FOR TERMINATIONS - APT. IN BACK NOT WIRED 5. PLANS NOT ACCURATE 6. A REINSPECTION FEE WILL BE ASSESSED NEXT INSP. IF NO COMPLIANCE 7. USE QUALIFIED ELECTRICIAN OR LICENSED CONTR. |