Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. USE PROPER CONNECTORS FOR CABLES ENTERING ENCLOSURES. 2. IDENTIFY PANEL DIRECTORIES 3. NEUTRAL NOT TO SHARE WITH ANOTHER CONDUCTOR IN GROUND BAR 4. HAVE INSULATION, NOT CONDUCTOR UNDER TERMINATION 5. SEAL UNUSED OPENINGS 6. BRANCH CKT CONDUCTORS NOT ALLOWED IN SAME ENCLOSURE WITH SERVICE CONDUCTORS. 7. CAN'T LOCATE GROUND RODS, WATER OR GAS BOND 8. INSTALL GASKETS FOR W.P J-BOX COVERS 9. UNIT #1 NEED MINIMUM 100 AMP MAIN, AND HOLDDOWN KIT 10. UNIT #2 MIN. 100 AMP. MAIN 11. PROVIDE ALL INTERIOR ACCESS 12. CHECK WIRING TO THESE UNITS, NOT WIRE AS SERVICE NOW, FED FROM BREAKER @ WELL PANEL2 PARTIAL INSPECTION ONLY |