Permit: T07EL00574

Parcel: 107141740

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/21/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. USE PROPER CONNECTORS FOR CABLES ENTERING ENCLOSURES.
2. IDENTIFY PANEL DIRECTORIES
3. NEUTRAL NOT TO SHARE WITH ANOTHER CONDUCTOR IN GROUND BAR
4. HAVE INSULATION, NOT CONDUCTOR UNDER TERMINATION
5. SEAL UNUSED OPENINGS
6. BRANCH CKT CONDUCTORS NOT ALLOWED IN SAME ENCLOSURE WITH SERVICE CONDUCTORS.
7. CAN'T LOCATE GROUND RODS, WATER OR GAS BOND
8. INSTALL GASKETS FOR W.P J-BOX COVERS
9. UNIT #1 NEED MINIMUM 100 AMP MAIN, AND HOLDDOWN KIT
10. UNIT #2 MIN. 100 AMP. MAIN
11. PROVIDE ALL INTERIOR ACCESS
12. CHECK WIRING TO THESE UNITS, NOT WIRE AS SERVICE NOW, FED FROM BREAKER @ WELL PANEL2

PARTIAL INSPECTION ONLY