Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/15/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) IDENTIFY EQUIPMENT GROUND FOR FEEDER 2) SECURE BOND WIRE TO STRUCTURE AND TIGHTEN CLAMPS |
|
| 06/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED AN EQUIPMENT GROUND RUN TO MAIN HOUSE WITH FEEDER CONDUCTORS - NEC 250.32 B1 2. PROVIDE A LISTED BRACE/GUY KIT FOR MAST - NEC 230.28 3. BOND METAL PIPING TO SERVICE - NEC 250.104 4. GROUND RODS TO BE MINIMUM 6' APART - NEC 250.56 AND DRIVE FLUSH TO GRADE - NEC 250.536 5. PROPERLY ATTACH G.E.C TO ACORNS & TIGHTEN - NEC 110.3B 6. NEED BUSHING #4 AND LARGER CONDUCTOR - NEC 300.5 7. STRAP PVC'S INTO PANELS 8. INSTALL SERVICE CONDUCTORS - NEC 230 9. SECURE SERVICE TO STRUCTURE BETTER - NEC 110.13 10. NEED GROUND RODS @ MAIN HOUSE SUB-PANEL AND SEPARATE GROUNDS AND NEUTRALS - NEC 250.32, 250.142 B 11. VERIFY UNDERGROUND FEEDERS ARE RATED FOR DIRECT BURIAL - I CAN'T READ MARKINGS. |