Permit: T07EL00554

Parcel: 123060160


Addresses:

2001 E LEE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/15/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) IDENTIFY EQUIPMENT GROUND FOR FEEDER
2) SECURE BOND WIRE TO STRUCTURE AND TIGHTEN CLAMPS
06/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED AN EQUIPMENT GROUND RUN TO MAIN HOUSE WITH FEEDER CONDUCTORS - NEC 250.32 B1
2. PROVIDE A LISTED BRACE/GUY KIT FOR MAST - NEC 230.28
3. BOND METAL PIPING TO SERVICE - NEC 250.104
4. GROUND RODS TO BE MINIMUM 6' APART - NEC 250.56 AND DRIVE FLUSH TO GRADE - NEC 250.536
5. PROPERLY ATTACH G.E.C TO ACORNS & TIGHTEN -
NEC 110.3B
6. NEED BUSHING #4 AND LARGER CONDUCTOR - NEC 300.5
7. STRAP PVC'S INTO PANELS
8. INSTALL SERVICE CONDUCTORS - NEC 230
9. SECURE SERVICE TO STRUCTURE BETTER - NEC 110.13
10. NEED GROUND RODS @ MAIN HOUSE SUB-PANEL AND SEPARATE GROUNDS AND NEUTRALS - NEC 250.32, 250.142 B
11. VERIFY UNDERGROUND FEEDERS ARE RATED FOR DIRECT BURIAL - I CAN'T READ MARKINGS.