Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED 8' CLEARANCE ABOVE ROOF ON SERVICE CONDUCTORS PER NEC 230.24 2. PROTECT ROMEX CABLE ENTERING 1/2" EMT PER NEC 300.15 3. NEUTRAL CONDUCTORS FOR STOVE CKT & INSIDE PANEL NEED TO BE CONNECTED TO NEUTRAL BAR AT OUTSIDE SUB-PANEL. CANNOT BE TERMINATED ON GROUND BAR 4. MAY NEED MAST BRACING IN MUST >36" ABOVE ROOF IF REQUIRED USE LISTED MAST BRACING. 5. SERVICE ENERGIZED PRIOR TO APPROVALS. |