Permit: T07EL00550

Parcel: 127080790


Addresses:

5441 E 7TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/03/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED 8' CLEARANCE ABOVE ROOF ON SERVICE CONDUCTORS PER NEC 230.24
2. PROTECT ROMEX CABLE ENTERING 1/2" EMT PER NEC 300.15
3. NEUTRAL CONDUCTORS FOR STOVE CKT & INSIDE PANEL NEED TO BE CONNECTED TO NEUTRAL BAR AT OUTSIDE SUB-PANEL. CANNOT BE TERMINATED ON GROUND BAR
4. MAY NEED MAST BRACING IN MUST >36" ABOVE ROOF
IF REQUIRED USE LISTED MAST BRACING.
5. SERVICE ENERGIZED PRIOR TO APPROVALS.