Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/05/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) 2ND GROUND ROD MUST BE FLUSH WITH FINISHED GRADE 2) OK NOTE #3 3) CALL FOR FINAL INSPECTION AFTER TIE IN |
|
| 04/17/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RODS MUST BE MIN. 6' APART PER ART. 250 2. RISER CONDUIT BRACE MUST BE A LISTED ASSEMBLY HOMEMADE OUT OF BENT EMT NOT APPROVED 3. CHANGE PERMIT DESCRIPTION TO 100 AMP. |