Permit: T07EL00544

Parcel: 136383270


Addresses:

3821 S POINCIANA DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED PANEL DIRECTORY PER NEC 408.4
2. LABEL SERVICE DISCONNECT PER NEC 230.70
3. PROVIDE LISTING OF SPLIT BOLT CONNECTOR. LOOKS TO HAVE EXCEEDED NUMBER OF WIRES ALLOWED. NEC 110.3
4. HAVE DISSIMILAR METALS CONNECTED AT SPLIT BOLT
NEC 110.14
5. INSTALL MAIN BONDING JUMPER PER NEC 250.28
6. BOND NIPPLE & SERVICE RISER PER NEC 250.92 & 250.102
7. INSTALL BREAKERS LISTED FOR USE IN PANEL - NEC 110.3
8. NO MORE THAN ONE CONDUCTOR UNDER LUG AT GROUND ROD NEC 250.70
9. CONNECT GROUND WIRE TO BELL BOX
10. CONNECT GROUNDS TO GROUND BAR/NEUTRAL BAR
11. REMOVE PAINT AT WATER BOND CONNECTION PER
NEC 250.12
12. PLEASE VERIFY PERMIT FOR NEW ROOFTOP UNIT
13. PLEASE VERIFY PERMIT FOR NEW WATER HEATER.