Permit: T07EL00543

Parcel: 12213016B


Addresses:

4206 E BELLEVUE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
CORRECTION ON NEW WIRING BPI CHRIS BATES ELECTRICAL AC PERMIT APPROVED
04/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO PERMITS ON RECORD FOR WORK DONE TO INTERIOR
A PERMIT WILL BE NEEDED AND WALLS OPENED FOR INSPECTION.
2. FINISH PREVIOUS WORK
04/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLEASE VERIFY PERMIT FOR NEW ROOFTOP A/C UNIT
2. LABEL CKT'S IN PANEL
3. INSTALL BUBBLE COVER ON NEW GFCI RECEPT UNDER PANEL NEC 406.8
4. CANNOT VERIFY GAS & WATER BOND
5. IDENTIFY NEUTRAL FOR 50A CKT PER NEC 200.6
6. VERIFY PROPER GROUND SIZE FOR 50A CKT PER
NEC 250.122
7. INSTALL LISTED EMT CONNECTOR ON 1 1/2 EMT
CANNOT USE CHASE NIPPLE.
8. COMPLETELY DRIVE GROUND RODS PER NEC 250.53
9. NEED MIN. 18" CLEARANCE ABOVE ROOF ON SERVICE DROP CONDUCTORS PER NEC 230.24
10. COULD NOT FIND COMBINATION LOCK BOX. WHAT NEEDS TO BE LOOKED AT IN HOUSE?