Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00532
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OPEN CEILING TILES & HAVE LADDER ON SITE FOR CEILING INSPECTION. 2. RECEPTACLE AT ONE WORK STATION HAS NO POWER 3. INSTALL APPROVED HANDLE TIE FOR WATER HEATER BREAKERS. 4. FLEXIBLE CORD CANNOT BE USED FOR CONNECTION OF RECEPTACLES. |