Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/24/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS 250.64 - USE A IRREVERSIBLE SPLICE |
|
| 12/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE BREAKERS LISTED BY MANUFACTURE 2. IDENTIFY GROUNDED CONDUCTOR 200.7 ENTIRE LENGTH RACEWAY 3. MAINTAIN WORKING CLEARANCES 110.26 #5 PREVIOUS INSPECTIONS. |
|
| 06/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* FINISH PREVIOUS ITEMS 1, 2, 3 & 5 |
|
| 03/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE VERIFY PERMIT FOR NEW ROOFTOP A/C UNIT 2. INSTALL LISTED MAST BRACING PER NEC 230.28 CANNOT USE EMT STRAP 3. GROUND RODS TO BE MIN. 6' APART PER NEC 250.53 4. LABEL CIRCUITS IN PANEL 5. NEED WORKING CLEARANCE IN FRONT OF PANEL PER NEC 110.26 6. SERVICE ENERGIZED PRIOR TO APPROVALS |