Permit: T07EL00531

Parcel: 133181620


Addresses:

7042 E 4TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/24/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/13/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
GROUNDING ELECTRODE CONDUCTOR TO BE
CONTINUOUS 250.64 - USE A IRREVERSIBLE SPLICE
12/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE BREAKERS LISTED BY MANUFACTURE
2. IDENTIFY GROUNDED CONDUCTOR 200.7 ENTIRE LENGTH RACEWAY
3. MAINTAIN WORKING CLEARANCES 110.26 #5 PREVIOUS INSPECTIONS.
06/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
FINISH PREVIOUS ITEMS 1, 2, 3 & 5
03/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLEASE VERIFY PERMIT FOR NEW ROOFTOP A/C UNIT
2. INSTALL LISTED MAST BRACING PER NEC 230.28
CANNOT USE EMT STRAP
3. GROUND RODS TO BE MIN. 6' APART PER NEC 250.53
4. LABEL CIRCUITS IN PANEL
5. NEED WORKING CLEARANCE IN FRONT OF PANEL PER
NEC 110.26
6. SERVICE ENERGIZED PRIOR TO APPROVALS