Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES 1. WIRING IN PANEL NOT MADE UP YET 2. SEE NOTE #2, #3, #4 3. A REINSPECTION FEE WILL BE ASSESSED NEXT INSPECTION IF NO COMPLIANCE. |
|
| 04/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FOR A 100 AMP SERVICE, A 100 AMP METER BASE IS REQUIRED, 2" RIGID RISER CONDUIT. 2. RISER SUPPORT BRACE MUST BE A LISTED ASSEMBLY. HOMEMADE OUT OF BENT EMT CONDUIT NOT APPROVED. 3. MC CABLE MUST BE SUPPORTED TO STRUCTURE WITHIN 12" OF TERMINATIONS & AT 6' INTERVALS PER NEC. 4. WIRING RUN BEHIND PANEL NOT TO CODE OBTAIN THE SERVICES OF A QUALIFIED ELECTRICIAN. 5. OBTAIN SERVICE UPGRADE PERMIT & INSTALL PER CODE |